| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/22/2016 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 01/25/2016 | KEN BROUILLETTE | FIRE | REVIEW | Completed | PUBLIC SCHOOL MUST BE REVIEWED BY STATE FIRE MARSHAL |
| 01/25/2016 | CPIERCE1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | No impact fees on solar permits. |
| 02/10/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A-1.0; CODE DATA: PLEASE INDICATE ON EACH STRUCTURE ARRAY THE NUMBER OF SOLAR MODULES. 2. GEOTECHNICAL REPORT: THIS REPORT WAS MADE FOR ONE AND TWO STORY MASONRY BUILDINGS AT THIS SITE. PLEASE PROVIDE ADDITIONAL INFORMATION FOR DRILLED PIER FOOTINGS. 3. SHEET S1; GENERAL STRUCTURAL NOTES (FOUNDATIONS): THE SOIL REPORT JOB NUMBER LISTED ON THE DRAWINGS DOES NOT MATCH THE REPORT NUMBER ON THE GEOTECHNICAL REPORT. PLEASE CLARIFY AND REVIEW THE FOUNDATION DESIGN IN THE STRUCTURAL CALCULATIONS AS REQUIRED. 4. SHEETS S3 THROUGH S6 (SECTION A); STRUCTURAL CALCULATIONS (SHEET 25): THE CALCULATIONS INDICATE THE BEAMS (M2 AND M3) ARE EACH 18.271' LONG (36.542' TOTAL). THE SECTION A INDICATES A BEAM LENGTH THAT IS GREATER THAN THE 36.542'. PLEASE CLARIFY. 5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 02/16/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/18/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |