| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 01/27/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a site drawing showing the size, route, and slope of the building sewer and the location of its connection to the public sewer. Reference: Section 107.2.1, IBC 2012. 2. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2012, for mercantile occupancy (a bottled water dispenser is not recognized as a substitute for a drinking fountain). Reference: Sections 1109.5 and 2902.1, IBC 2012. 3. On the Plumbing Fixture Schedule, service sink P3 does not show any drainage fixture units but a direct connection to the building drainage system for the fixture is shown in the soil and vent riser diagram. Revise the schedule to include the drainage fixture units for P3. Reference: Section 301.3, IPC 2012. 4. Verify that the proposed cabinet can provide access and working space for the water heater, the expansion tank, and the required valves. Reference: Section 501.4, IPC 2012. 5. Revise the termination point of the T&P relief discharge piping so that a discharge is readily visible to the building occupants. Reference: Section 504.6 (7), IPC 2012. 6. For the use of PEX tubing, provide a branch tube sizing chart showing the correct size of PEX tubing to be used as a substitute for the CPVC pipe sizes shown on the drawings. Reference: Sections 303.2 and 604.3, IPC 2012. 7. Verify that the free area of the proposed vent cap for the termination of the plumbing vent is at least equal to the open area of the required plumbing vent. Reference: Sections 904.1.2 and 906.2, IPC 2012. 8. Provide the location and size of the downspouts for the roof gutter. Reference: Sections 1106.1 and 1106.6, IPC 2012. |
| 01/27/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
| 01/28/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. What portion of the main sales area is allocated to animal holding (similar to the back area) and thus requiring exhaust? Reference: Section 403.3, IMC 2012. 2. Show the U-factors for the roof and wall sections on the drawings. Reference: Section C103.2, IECC 2012. |
| 02/09/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G1.0; DRINKING FOUNTAIN: THE WATER DISPENSER MUST BE A SINGLE POINT OF USE WATER DISPENSER THAT IS CONNECTED DIRECTLY TO A WATER LINE. 2. SHEET G1.0; EXIT PLAN: SINCE THE EXIT INTO THE COURTYARD IS NOT ACCESSIBLE DUE TO THE GRATING (SEE 10/A1.0), PLEASE INDICATE ON THE DRAWINGS THAT SIGNAGE PER THE IBC SECTION 1110.1 WILL BE REQUIRED, STATING IT IS NOT AN ACCESSIBLE ENTRANCE/EXIT. 3. SHEET A1.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE ELEVATION 4, DETAILS 9 AND 10, AND SECTION 9. 4. SHEET A1.1; SITE KEYNOTES: NOTE 5 REFERENCES DETAIL 5/A1.0. PLEASE REVISE THE DETAIL REFERENCE. 5. SHEET A1.1; SITE KEYNOTES: NOTE 7 REFERENCES DETAIL 7/A1.0. PLEASE REVISE THE DETAIL REFERENCE. 6. SHEET A1.1; SECTIONS 6 AND 7: PLEASE PROVIDE THE FOUNDATION SIZE AND DEPTH. 7. SHEET A1.2; PLAN 1: TWO SECTION CUTS REFERENCE 1/A1.0. PLEASE REVISE THE SECTION REFERENCES. 7. SHEET A1.2; ELEVATION 8: THIS SHOULD BE TITLED 'EAST SECTION'. PLEASE REVISE AND CUT THE SECTION ON THE PLAN. 8. SHEET A1.2; DETAILS 6, 7, 9, AND 10: PLEASE INDICATE THESE DETAILS ON THE PLAN. 9. SHEET A2.0; FLOOR PLAN: PER THE IBC TABLE 2902.1, A HIGH/LOW DRINKING FOUNTAIN OR SINGLE POINT OF USE WATER DISPENSER (CONNECTED DIRECTLY TO A WATER LINE) IS REQUIRED. PLEASE PROVIDE ON THE PLAN. 10. SHEET A5.2; TRELLIS SECTION 1: DETAILS 10 AND 12 ON THIS SECTION SHOULD BE REVISED TO 11 AND 10. PLEASE VERIFY. 11. SHEET A7.0; DOOR HARDWARE SCHEDULE: THE LAST HARDWARE GROUP IS REFERENCED AS 'G'. PLEASE REVISE TO 'H'. 12. SHEET S1.0; GENERAL STRUCTURAL NOTES (FOUNDATIONS): PLEASE PROVIDE ONE COPY OF THE GEOTECHNICAL REPORT FOR REVIEW. 13. SHEET S2.1; ROOF FRAMING KEYNOTES: NOTE 5 INDICATES TRELLIS PURLINS AND BRACING PER ARCHITECTURAL, WHILE SHEET A3.0 (KEYNOTE 28) INDICATES TO SEE STRUCTURAL FOR BRACING DETAILS. DETAILS 10, 11, 13, AND 14 ON SHEET A5.2 SHOW THE BRACING, BUT NO INDICATION OF HOW THE BRACING IS CONNECTED TO THE STRUCTURAL BEAMS. PLEASE CLARIFY AND REVISE AS REQUIRED. 14. STRUCTURAL CALCULATIONS; SHEET 33: PLEASE VERIFY WHERE THIS BEAM IS LOCATED ON THE PLANS. 15. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 02/10/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 02/11/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please verify compliance with sec. 402.1 ( color source temperature ] for exterior lighting per the City of Tucson/Pima County Outdoor Lighting Code. |