Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM00444
Parcel: 13317064C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM00444
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2016 MICHAEL ST. PAUL ZONING REVIEW Approved
01/20/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/20/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/20/2016 LOREN MAKUS ENGINEERING REVIEW Approved
01/20/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET TS1; GENERAL BUILDING SUMMARY: THE SPRINKLER SYSTEM REFERENCES THE IBC SECTION 1004.3.2.1. PLEASE REVISE.
2. SHEET TS1; GENERAL BUILDING SUMMARY: THE TYPE OF CONSTRUCTION REFERENCES THE IBC SECTION 503. PLEASE REVISE.
3. SHEET TS1; CODE STUDY: THE SPRINKLERS (#5) REFERENCE THE IBC TABLE 1014.3, 1018.1, AND 1018.2. PLEASE REVISE.
4. SHEET A1; FLOOR PLAN: A NOTE IN CORRIDOR 100 INDICATES AN EXISTING DRINKING FOUNTAIN AND SERVICE SINK IN THE EXISTING LOBBY. PLEASE INDICATE IN THIS NOTE THE MAXIMUM TRAVEL DISTANCE TO EACH FROM THIS OFFICE, AND INDICATE THAT IT MEETS THE REQUIREMENTS OF THE IBC SECTIONS 2902.3.2.1 AND 2902.5.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/20/2016 ROBERT SHERRY WATER REVIEW Completed
01/20/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show that the required drinking fountains are available within the prescribed distance.
2. Correct the HW/HWR line types over room 120-122 on P2 and in riser 2/P3.
01/20/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/21/2016 KEN BROUILLETTE FIRE REVIEW Approved