Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T16CM00349
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/16/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
02/23/2017 | ROBERT SHERRY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Provide a complete geotechnical report for the proposed location of the replacement light and communication monopole. The submitted geotechnical report does not include four of the seven sections of the report, including the specific recommendations for the foundation of the replacement monopole which are referenced in the structural calculations. (The submitted report also incorrectly identifies the site as being located in the Town of Oro Valley and calls out the monopole as being only 80-feet tall.) |
02/28/2017 | FRODRIG2 | COMMUNICATIONS | REVIEW | Approved | LETTER SENT TO RECORDS |
03/15/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/19/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |