Permit Number: T16CM00349
Parcel: 136290020

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T16CM00349
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2016 MARTIN BROWN FIRE REVIEW Approved
01/27/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: THIS IS A NEW 82'-6" TALL LIGHT POLE WITH NEW ANTENNAS. THE $25,000 VALUATION WAS GIVEN TO THE CITY OF TUCSON AS AN ANTENNA SWAP ON AN EXISTING POLE. PLEASE PROVIDE AN ADJUSTED VALUATION FOR THIS PROJECT.
01/28/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide for a special inspection and full compliance with the Tucson/ Pima County Outdoor Lighting Code.
Sec. 106.2.2.
#2. Provide a complete electrical detail or plan showing approved wiring methods to accomadate the installation of the new light pole.
Ref:2012 IBC sec.107.2.1, 2011 NEC. Tucson /Pima County Outdoor Lighting Code can be downloaded from www.tucsonaz.gov
02/08/2016 FRODRIG2 COMMUNICATIONS REVIEW Approved LETTER SENT TO RECORDS

Final Status

Task End Date Reviewer's Name Type of Review Description
02/14/2017 LBOJORQ1 OUT TO CUSTOMER Completed