Permit Number: T16CM00345
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM00345
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2016 STEVE SHIELDS ZONING REVIEW Approved
01/14/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide ventilation calculations for the suite per Section 403.3, IMC 2012.
2. Provide an economizer for the proposed Rooftop unit. Reference: Section C403.3.1, IECC 2012.
01/14/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
01/14/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please update the electrical registrant expiration date.
01/14/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/14/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/14/2016 ROBERT SHERRY WATER REVIEW Completed
01/14/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET ADA1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THIS SHEET.
2. SHEET ADA1: A NOTE INDICATES REQUIREMENTS OF THE 2010 ADA STANDARDS WERE USED FOR THIS PROJECT. PLEASE REVISE TO THE 2009 ICC/ANSI A117.1. INDICATE ON THE TOILET SIDE WALL A VERTICAL GRAB BAR PER THE ICC/ANSI FIGURE 604.5.1 (AND SHEET A5a).
3. SHEET A3; SECTIONS 2, 3, AND 4: ARE THE VERTICAL AND LATERAL BRACING MEMBERS EXISTING? A NOTE INDICATES TO SEE STRUCTURAL, BUT NO STRUCTURAL SHEETS ARE INCLUDED IN THIS SUBMITTAL. PLEASE VERIFY.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/15/2016 MARTIN BROWN FIRE REVIEW Approved