Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM00345
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/14/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
01/14/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide ventilation calculations for the suite per Section 403.3, IMC 2012. 2. Provide an economizer for the proposed Rooftop unit. Reference: Section C403.3.1, IECC 2012. |
01/14/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please update the electrical registrant expiration date. |
01/14/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
01/14/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET ADA1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THIS SHEET. 2. SHEET ADA1: A NOTE INDICATES REQUIREMENTS OF THE 2010 ADA STANDARDS WERE USED FOR THIS PROJECT. PLEASE REVISE TO THE 2009 ICC/ANSI A117.1. INDICATE ON THE TOILET SIDE WALL A VERTICAL GRAB BAR PER THE ICC/ANSI FIGURE 604.5.1 (AND SHEET A5a). 3. SHEET A3; SECTIONS 2, 3, AND 4: ARE THE VERTICAL AND LATERAL BRACING MEMBERS EXISTING? A NOTE INDICATES TO SEE STRUCTURAL, BUT NO STRUCTURAL SHEETS ARE INCLUDED IN THIS SUBMITTAL. PLEASE VERIFY. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
01/14/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/14/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
01/14/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/15/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |