| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/25/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 02/01/2016 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T16CM00285 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code, 2012 International Fire Code, 2011 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. DIAGRAMS / CALCULATIONS 1. Show the sum of the main and backfeed breakers not exceeding 120% of the busbar rating, NEC 690.64 & 705.12 (D). Main breaker replacement may not negatively affect the equipment integrity or listing, NEC 110.3. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |