Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T16CM00216
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2016 STEVE SHIELDS ZONING REVIEW Approved
01/15/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
01/20/2016 DSANTAC2 BUILDING-RESIDENTIAL REVIEW Reqs Change Please address the following plan review comments, also provide a written response.
#1. The POWERBLASTER and circuit breaker is not shown on the three line diagram.
#2. Provide load calc's for the existing 125 amp service panel and the new sub- panel to verify that de-rating to a 100 amp main breaker for the main panel, and the 25 amp breaker for the sub- panel are adequate to handle the loads. Also indicate the circuit breaker sizes as well as the total load for the sub- panel.
#3. The encircled note #5 below the three line diagram does not coincide with the number of circuit breakers shown in the sub- panel. Plan Sheet PV6.
#4. For future reference, the warning label as required per NEC 690.17 should be provided on the inverters when equipped with AC/DC disconnects as the possibility may exist at this location.
Ref: 2012 IBC sec. 107.2.1, 2011 NEC, 2012 IRC sec. R106.1.1