Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - RES
Permit Number - T16CM00216
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/15/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/15/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 01/20/2016 | DSANTAC2 | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Please address the following plan review comments, also provide a written response. #1. The POWERBLASTER and circuit breaker is not shown on the three line diagram. #2. Provide load calc's for the existing 125 amp service panel and the new sub- panel to verify that de-rating to a 100 amp main breaker for the main panel, and the 25 amp breaker for the sub- panel are adequate to handle the loads. Also indicate the circuit breaker sizes as well as the total load for the sub- panel. #3. The encircled note #5 below the three line diagram does not coincide with the number of circuit breakers shown in the sub- panel. Plan Sheet PV6. #4. For future reference, the warning label as required per NEC 690.17 should be provided on the inverters when equipped with AC/DC disconnects as the possibility may exist at this location. Ref: 2012 IBC sec. 107.2.1, 2011 NEC, 2012 IRC sec. R106.1.1 |