Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM00188
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/05/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. AS per the KEYED NOTE #18 on plan sheet PV- 30. Provide detailed information as to how the load side PV interconnection ( Tap ) is to be performed as directed per the manufacturer of the electrical equipment, also verifying, this installation will not compromise the performance and listing of this equipment. Provide a shop drawing or detailed instructions by the manufacturer, stamped by the registrant of record or added to the electrical plans. Or provide the wiring method, including hardware to be utilized to accomplish the tap along with a field evaluation and re-listing by a NRTL. #2. Show a grounding electrode system for the new 225 kva transformer at west building. Show conductor size and type, and type of electrode. Ref: 2012 IBC, 2011 NEC. |