Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T16CM00188
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/14/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/28/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/03/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments, also provide a written response. #1. Ref: Plan Sheet PV-3.0. The note shown by the existing electrical equipment describes replacing the existing six service disconnects with new service raceway. For clarification, provide a complete one line diagram of the service and associated equipment, conduit, conductor sizes and types. Include all the information as required per City of Tucson Commercial Plan Submittal Requirements . These requirements can be downloaded from, www.tucsonaz.gov/pdsd, go to Development and Permits, click on, Preparing Plans and Permit, then go to Preparing your Plans for a Building Permit, go to Commercial Permits, then to Commercial Plan Review, Electrical items #2. Ref; 2012 IBC sec. 107.2.1 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/24/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |