Permit Number - T16CM00135
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/12/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/12/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/12/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/12/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments.Also provide a written response. #1. Please indicate feeder conduit and conductor sizes and types between panel 'SS1' and the 75 KVA tronsformer. #2. 75 KVA transformer grounding to include, water pipe, and building steel. #3. Panel 'SS' requires a main circuit breaker per 408.36 NEC. #4. Feeder conductor rating and sizes on secondary side of the 75 KVA transformer do not coincide with the amp rating and load calc for panel 'SS'. Ref: IBC sec.107.2.1, 2011 NEC. |
| 02/12/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |