Permit Number: T16CM00135
Parcel: 10701040B

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM00135
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/12/2016 ROBERT SHERRY WATER REVIEW Completed
02/12/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/12/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments.Also provide a written response.
#1. Please indicate feeder conduit and conductor sizes and types between panel 'SS1' and the 75 KVA tronsformer.
#2. 75 KVA transformer grounding to include, water pipe, and building steel.
#3. Panel 'SS' requires a main circuit breaker per 408.36 NEC.
#4. Feeder conductor rating and sizes on secondary side of the 75 KVA transformer do not coincide with the amp rating and load calc for panel 'SS'.
Ref: IBC sec.107.2.1, 2011 NEC.
02/12/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed