Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM00135
Parcel: 10701040B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM00135
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2016 LOREN MAKUS ENGINEERING REVIEW Approved
01/20/2016 KEN BROUILLETTE FIRE REVIEW Approved
01/22/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Show how hot water is to be supplied to the service sink located in the secure storage room.]
2. Comment not addressed. [Initial comment: Show how the water heater is to be supported.]
01/22/2016 ROBERT SHERRY WATER REVIEW Reqs Change Comment not addressed. [Initial comment: Verify that the water service has a backflow preventer.]
01/22/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Appeal pending. [Initial comment: Verify compliance with the energy code; existing shell building.]
02/03/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET CS-1; GENERAL NOTES (REFLECTED CEILING): NOTE 1 REFERENCES THE 2006 IBC. PLEASE REVISE.
2. SHEET CS-1; CODE REVIEW CHECKLIST: PLEASE ADD THE CONSTRUCTION TYPE ON THE DRAWING. IN ADDITION, INDICATE ON THE DRAWINGS THE CALCULATIONS FOR THE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES (WATER CLOSETS, LAVATORIES, DRINKING FOUNTAINS, AND SERVICE SINKS).
3. SHEET CS-1; CODE REVIEW CHECKLIST: PLEASE INDICATE ON THE DRAWING THE CALCULATIONS FOR THE ALLOWABLE AREA OF THE TOTAL BUILDING (76,000 SF IS INDICATED).
4. SHEET CS-1; CODE REVIEW CHECKLIST (OCCUPANT LOADS): NOTE 6 REFERENCES THE IBC SECTION 1003.2.2.2 FOR OCCUPANT LOADS. PLEASE REVISE THE REFERENCE.
5. SHEET CS-1; CODE REVIEW CHECK (OCCUPANT LOADS): NOTE 6 INDICATES SIX EXITS PROVIDED WITH 44" WIDTH. PLEASE REVISE THE TOTAL EXIT WIDTH.
6. SHEET A-2; FLOOR PLAN (SECURE STORAGE): THE INTERIOR WALLS REFERENCE KEYNOTE B, WHICH GIVES THE WALL STUD GAUGE AND SPACING, BUT DOES NOT INDICATE STUD SIZE. PLEASE PROVIDE OR ADD A REFERENCE.
7. SHEET A-2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE DOOR SCHEDULE, PLAN ELEVATIONS, AND ROOM NUMBERS.
8. SHEET A-2; PLAN KEYNOTES: MANY OF THESE NOTES ARE NOT INDICATED ON THE PLAN. PLEASE VERIFY AND REVISE. REFERENCE SHEET A-3 AS REQUIRED.
9. SHEET A-3; FLOOR PLAN: THE PLAN INDICATES 2X6 WALL IN SEVERAL LOCATIONS. PLEASE CLARIFY IF WOOD OR METAL STUDS WILL BE USED.
10. SHEET A-3; FLOOR PLAN: ARE THE WALLS WITH NO NOTATION TO BE 3 5/8" METAL STUDS OR WOOD STUDS? PLEASE CLARIFY.
11. SHEET A-3; FLOOR PLAN: THE HEIGHT OF THE SERVICE COUNTERS IN THE SHOWROOM MUST MEET THE ACCESSIBILITY REQUIREMENTS OF THE ICC/ANSI SECTION 904.3. PLEASE INDICATE ON THE DRAWINGS (42" HEIGHT IS INDICATED).
12. SHEET A-3; FLOOR PLAN: IS ANY OF THE EXTERIOR GLASS SHOWN ON THE PLAN NEW? PLEASE VERIFY.
13. SHEET A-5 (CEILING PLAN); SHEETS E1 AND E4 (FLOOR PLANS): PLEASE VERIFY THAT EXIT LIGHTING IS CONSISTENTLY SHOWN ON ALL PLANS.
14. SHEET A-6; DETAILS 2 AND 3: PLEASE INDICATE ON THE DETAILS THE WALL STUD SIZE (GAUGE AND SPACING GIVEN).
15. SHEET A-6; ELEVATION 4: PLEASE PROVIDE THE LUNCH ROOM ELEVATION.
16. GENERAL: PLEASE VERIFY THAT THERE ARE NO HAZARDOUS MATERIALS IN THE SECURE STORAGE SPACE THAT EXCEED THE LIMITATIONS OF THE IBC SECTION 307. PLEASE INDICATE THAT ANALYSIS OR STATEMENT ON THE DRAWINGS.
17. GENERAL: PLEASE VERIFY THE USE OF THE FRONT OF THE BUILDING AS BUSINESS. WITH A SHOWROOM, A POSSIBLE MERCANTILE USE COULD BE INCLUDED. THE PERMIT APPLICATION INDICATES RETAIL SALES AND WAREHOUSE.
18. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/06/2016 CPIERCE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
02/08/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment, also provide a written response.
#1. As per the last review, it was requested to provide complete information as required to provide a complete and code compliant electrical review.
These requirements can be downloaded from, www.tucsonaz.gov/pdsd, go to Development and Permits, click on, Preparing Plans and Permit, then go to Preparing your Plans for a Building Permit, go to Commercial Permits, then to Commercial Plan Review, Electrical items #2 and #3.
Ref; 2012 IBC sec. 107.2.1