Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM00135
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 01/08/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Verify compliance with the energy code; existing shell building. |
| 01/08/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a response. #1. Include all electrical equipment on the one line diagram including new panels, transformer, include feeders, conduits, conductors, sizes and types, fault currents and loads at new panels.Complete panel schedules. Ref: IBC 107.2.1, NEC |
| 01/08/2016 | ENEWCOM1 | FIRE | REVIEW | Needs Review | |
| 01/08/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 01/08/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Verify that the water service has a backflow preventer. |
| 01/08/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Show how hot water is to be supplied to the service sink located in the secure storage room. 2. Show how the water heater is to be supported. |
| 01/13/2016 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 01/15/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Needs Review |