Permit Number: T16CM00135
Parcel: 10701040B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM00135
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/08/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify compliance with the energy code; existing shell building.
01/08/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a response.
#1. Include all electrical equipment on the one line diagram including new panels, transformer, include feeders, conduits, conductors, sizes and types, fault currents and loads at new panels.Complete panel schedules.
Ref: IBC 107.2.1, NEC
01/08/2016 ENEWCOM1 FIRE REVIEW Needs Review
01/08/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
01/08/2016 ROBERT SHERRY WATER REVIEW Reqs Change Verify that the water service has a backflow preventer.
01/08/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show how hot water is to be supplied to the service sink located in the secure storage room.
2. Show how the water heater is to be supported.
01/13/2016 DAVID RIVERA ZONING REVIEW Approved
01/15/2016 LOREN MAKUS ENGINEERING REVIEW Needs Review