Permit Number: T16CM00066
Parcel: 14118533A

Review Status: Active

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM00066
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2016 KEN BROUILLETTE FIRE REVIEW Approved
01/11/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 9608 E. Old Vail Road - Ground Mounted Solar
T16CM00065 & T16CM00066
Building Plan (1st Review)

TRANSMITTAL DATE: January 11, 2016

1. The solar plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The proposed ground mounted solar field require a development package to be submitted and approved prior to the solar plans.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the solar plans cannot be approved by zoning.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/26/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S-302-A (FOOTING SCHEDULE); STRUCTURAL CALCULATIONS (ALTERNATE FOUNDATION DESIGN PAGE 1): THE FOOTING REINFORCMENT CALLED OUT IN THE SCHEDULE (6-#4 TOP AND BOTTOM OR 4-#5 TOP AND BOTTOM PERPENDICULAR TO THE POST WEB AND 4-#4 TOP AND BOTTOM OR 4-#5 TOP AND BOTTOM PARALLEL TO THE POST WEB) DOES NOT MATCH THE REINFORCEMENT INDICATED IN THE CALCULATIONS (8-#5 EACH WAY BOTTOM). PLEASE CLARIFY.
2. GENERAL: PLEASE PROVIDE A WRITTEN RESPONSE TO THE REVIEW COMMENT.
01/27/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide additional information for the supply side tap at the point of the PV interconnection ( LINE DIAGRAM ). Such as :
(a). What does Part Kit # 80247-533-5x consist of.
(b). Provide verification from the manufacturer of the service equipment that this tap kit is compatible with this equipment and will not compromise the listings or performance of the service equipment. Or provide for a field inspection of the work performed, and re-listing of the equipment by a NRTL .
Ref: IBC sec. 107.2.1, NEC art. 110.3, 690.
02/04/2016 ELIZABETH LEIBOLD ENGINEERING REVIEW Reqs Change DATE: February 4, 2016
TO: Michael Furrier P.E.
SUBJECT: Solar Project Engineering Review
ADDRESS: 9608 E OLD VAIL RD
LOCATION: T15S, R15E, Section 26
REVIEWER: Elizabeth Leibold P.E.
CASE: T16CM00065, T16CM00066
SUMMARY: PDSD Engineering Division has reviewed the plans for the Solar Project and does not recommend approval until the following comments are addressed. Project is located within the Julian Wash Watershed which is a Balanced Basin Management Watershed, and is impacted by the Rita Ranch Master Drainage Report and associated annexation Ordinance 6143. This project does not need to provide detention or retention for this portion of the watershed that enters the Regional Basin per the Rita Ranch Master Drainage Report.
COMMENTS:
1) UDC Sec.7.6.4.A.2, Admin Man Secs.2-06.4.7, 2-06.4.7.A.6: Address the following comments:
a) See Administrative Manual sections 2-06.4.3 and 2-06.4.7 for formatting and general notes required and other content information needed for the development package sheets. http://library.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/tucsonazunifieddevelopmentcode?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az
b) Label on planview for site and grading plan sheets, the following information:
i) Add note for total disturbance area.
ii) Add note for cut and fill quantities in cubic yards.
iii) The property is subject to Annexation (Ord.6142) requirements; provide the applicable annexation file number, in the lower right corner of each sheet.
iv) Label and delineate grading disturbance limits, clarifying areas that are to remain undisturbed (area west of solar panel phases.)
v) Clarify access areas:
(1) Delineate access lanes on planviews.
(2) Label access surface treatment material.
(3) Revise plans to clarify connection for access areas to existing pavement area and right of way.
vi) Disturbed areas are required to be reseeded, if gravel is not provided in disturbed areas. Show and label and add as notes to the cover sheet that there will be reseeding for all disturbed areas for this project. Some solar projects use a special desert reseed mix that has a short/low growth height, and others use gravel to reduce dust accumulation on panels; specify what will be used around/under panels on plans.
c) Tucson Code Chap.26 Art.2: For this solar project, a SWPPP and grading information under a Development Package application will be needed for resubmittal. Provide grading and SWPP plan sheets in development package set. Add the following note to SWPP sheet: Operator shall report to ADEQ any noncompliance (including spills) which may endanger human health or the environment. The operator shall orally notify the office listed below within 24 hours: Arizona Department of Environmental Quality, 1110 W. Washington, 5th floor (5515B-1), Phoenix, AZ 85007, Office: 602-771-4466; Fax 602-771-4505
d) Development Package may include site plan, grading plan, SWPP, and can show both phases of the project if a note is added that this permit is for phase 1. Later, a revision to the project may be submitted updating the note to state phase 2 and issued for second phase. Otherwise two development packages may be submitted for each phase.
For resubmittal, provide 2 sets of development package plans under development package application(s), 2 copies of SWPP reports or other documentation, and a response letter. If you have any questions, email me at elizabeth.leibold@tucsonaz.gov
Elizabeth Leibold, PE, CPM, CFM
Civil Engineer
Engineering Division
Development Services Department
City of Tucson

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2016 ANY REJECT SHELF RECEIVED