Permit Number: T16CM00015
Parcel: 10321671B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM00015
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2016 MICHAEL ST. PAUL ZONING REVIEW Approved
01/04/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
01/06/2016 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Passed
01/06/2016 ERIC NEWCOMB MECHANICAL-COMMERCIAL REVIEW Passed
01/06/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: PLEASE PROVIDE A VALUATION FOR THE LABOR AND MATERIALS FOR THIS PROJECT.
2. SHEET A02.00; SECTION D: PLEASE PROVIDE THE METAL STUD SPACING, DIAGONAL BRACING SIZE AND SPACING, AND THE CONNECTION OF THE METAL STUDS TO THE EXISTING STRUCTURE AND TO NEW METAL STUDS.
3. SHEET A02.00; SECTIONS B AND C: THE CITY OF TUCSON REQUIRES ALL LETTERING TO BE A MINIMUM OF 3/32' IN HEIGHT. PLEASE REVISE.
4. SHEET A09.100; PARTITION TYPE 1: PER THE IBC SECTION 1607.14, INTERIOR PARTITIONS MUST BE CAPABLE OF RESISTING A HORIZONAL LOAD OF 5 PSF. THE CEILING CAN NOT RESIST THIS LOAD. PLEASE PROVIDE DIAGONAL BRACING AT THE TOP OF THE WALL, INDICATING THE BRACING SIZE AND SPACING, AND THE CONNECTION OF THE BRACING TO THE EXISTING STRUCTURE ABOVE AND TO THE TOP OF THE PARTITION.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/06/2016 KEN BROUILLETTE FIRE REVIEW Approved
01/06/2016 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Passed
01/06/2016 ENEWCOM1 WATER REVIEW Passed
01/06/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed