Permit Number: T16BU01389
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T16BU01389
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2017 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Reqs Change Below are the BRC comments on the authorized repair submittal for COT ID# 367 at 3127 East Speedway Boulevard (T16BU01389).



Sheet 1 of 3



No comments.



Sheet 2 of 3



1, In 5th paragraph of Scope of Work, it still needs to be clarified whether 16d nail attachment of metal face panels to wood stringers is existing method of attachment or a proposed alteration; also clarify if there are pre-drilled nail holes on the panels or the nails are driven through the panels and include the number of nails per metal face panel section.



Sheet 3 of 3



No comments.



FIN.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/09/2017 QJONES1 APPROVAL SHELF Completed
10/09/2017 QJONES1 OUT TO CUSTOMER Completed
10/09/2017 QJONES1 REJECT SHELF Completed