Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change T16BU01301
Please address the following electrical plan review comments. Also provide a written response.
#1. Ref: TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. The Lumen calcs for total allowed lumens must be taken from option #1, #2, or #3 of table 401.1. All Residential Zoning is restricted to 1 or 2 family dwellings. Because the pool is a community pool it is considered commercial.
#2. Per plan notes DE3 and DE4, plan sheet SP-001. A total of 5 pool luminaires are being replaced and 1 new, 6 total. Verify that all are the same, or provide the additional luminaire information. Also verify lamp color temperature of the luminaires is in compliance with sec 402.1 (3500K).