| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | T16BU01301 Please address the following electrical plan review comments. Also provide a written response. #1. Ref: TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. The Lumen calcs for total allowed lumens must be taken from option #1, #2, or #3 of table 401.1. All Residential Zoning is restricted to 1 or 2 family dwellings. Because the pool is a community pool it is considered commercial. #2. Per plan notes DE3 and DE4, plan sheet SP-001. A total of 5 pool luminaires are being replaced and 1 new, 6 total. Verify that all are the same, or provide the additional luminaire information. Also verify lamp color temperature of the luminaires is in compliance with sec 402.1 (3500K). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/21/2016 | LBOJORQ1 | APPROVAL SHELF | Completed |
| 11/21/2016 | LBOJORQ1 | OUT TO CUSTOMER | Completed |
| 11/21/2016 | LBOJORQ1 | REJECT SHELF | Completed |