Permit Review Detail
Review Status: Completed
Review Details: POOL - SPA
Permit Number - T16BU01301
Review Name: POOL - SPA
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/16/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide complete compliance with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. See section 401.2.1 for lumen calc for pool lighting, to be included in total exterior lumen calculation per Chapter 1 and 4. #2. Provide a complete luminaire schedule. #3. Provide for all the grounding required per NEC sec 680.6, including Equipotential Bonding as required per art 680.26 NEC. |
| 11/16/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |