Review Details: BILLBOARD - BLDG30days

Permit Number - T16BU01038
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2016 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Reqs Change Below are comments on the authorized repair submittal for COT ID# 483 at 4947 North Oracle Road (T16BU01038).



Sheet 1 of 4



No comments.



Sheet 2 of 4



1. In Safety Cable Attachment Detail, resolve conflict where 3/8-inch wire is indicated and Sheet 1 of Calcs where 1/4-in wire is indicated; also specify which of the four types of 7X19 cable shown in the calcs is to be used.



Sheet 3 of 4



No comments.



Sheet 4 of 4



No comments.



FIN.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/17/2016 LBOJORQ1 APPROVAL SHELF Completed
11/17/2016 LBOJORQ1 OUT TO CUSTOMER Completed
11/17/2016 LBOJORQ1 REJECT SHELF Completed