| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/01/2016 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Reqs Change | The following comments are from the BRC. Below are comments on the authorized repair submittal for COT ID# 49 at 713 West Speedway Boulevard (T16BU00853). Sheet 1 of 3 No comments. Sheet 2 of 3 1. In 5th paragraph of Scope of Work or elsewhere on plan as may be appropriate, clarify that apron stringer replacement bolts will utilize same bolt holes as existing and that apron position relative to billboard structure will otherwise remain same. 2. Provide side view of Safety Cable Attachment Detail with vertical and horizontal dimensions setting the location of the eye bolt hole 3. Provide structural calcs for added cable Sheet 3 of 3 1. In Poster Panel Top View and elsewhere on plan as appropriate, clarify what Existing Stringer Mounting Bracket and provide with proper designation line (or delete if part does not exist). FIN. |