Permit Number: T16BU00725
Parcel: 11708164B

Address:
501 W 18TH ST

Review Status: Completed

Review Details: WALLS

Permit Number - T16BU00725
Review Name: WALLS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2016 ANDREW CONNOR ZONING REVIEW Approved
05/06/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also include a written response.
#1. Designate a circuit number and panel for the branch circuit feeding the electrical gate equipment. Include a complete panel schedule and load calc.
#2. Provide for disconnecting means within site of the equipment if not integral with the equipment.
Ref: 2012 IBC sec. 107.2.1, 2011 NEC art. 408.4, 422.31, 430.
#2.
05/06/2016 LOREN MAKUS ENGINEERING REVIEW Approved
05/06/2016 ANDREW CONNOR NPPO REVIEW Passed
05/09/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1; DETAIL 4: THE FOOTING INDICATES TO SEE STRUCTURAL. PLEASE INCLUDE.
2. SHEET A1: PLEASE PROVIDE A STRUCTURAL DETAIL FOR THE NEW 4X4 STEEL POSTS FOUNDATION.
3. SHEET A1: PLEASE ADD STRUCTURAL CALCULATIONS FOR THE FOUNDATIONS LISTED IN COMMENTS 1 AND 2.