Permit Number: T16BU00494
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T16BU00494
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/06/2016 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Reqs Change BRC Comments

Sheet 1 of 3
1. In site plan with aerial photograph underlay, show north property line and provide dimension from billboard footprint to north property line to more clearly set location of the billboard,.

Sheet 2 of 3
1. In boxed note, delete subsection “J” and insert “I” (the former only relates to the special allowance for the addition of rear catwalks on COT #540, which is not being proposed per the submitted plans; although “J” specifies replacement of wood catwalks with metal catwalks, the like to like replacement and the foregoing of the allowed upgrade to metal will be accepted).

2. In Catwalk and Ledger Mounting Detail, add horizontal dimensions for the wood catwalk pieces relative to the outer edge of the catwalk ledger and the near face of the I-beam.

3. Add plan view detail showing all catwalk ledgers and all wood catwalk pieces with appropriate dimensions, including overall length and distance from outer edge of catwalk to near I-beam face.

4. Add note that unused ledger clips affixed to I-beams to be removed.

Sheet 3 of 3
1. Add standard Stringer Mounting Details (indicating to remain).

FIN.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/20/2016 RBENT1 OUT TO CUSTOMER Completed