Permit Number: T16BU00284
Parcel: 10706005B

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T16BU00284
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/29/2016 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Reqs Change BRC Comments
Below are comments on the authorized repair submittal for COT ID# 175 at 1010 West Miracle Mile Strip (T16BU00284).

Sheet 1 of 3
No comments.

Sheet 2 of 3
1. In 1st & 10th paragraphs of Scope of Work, indicate that rigid conduit light fixture support arms are to be removed and reinstalled (in addition to the light fixture) and that conduit straps are to be replaced (consistent with Side View (North Elevation) on Sheet 3).

2. In 2nd paragraph of Scope of Work, delete per face reference (as there is only one face).

3. In 3rd paragraph of Scope of Work, delete last sentence regarding panel clips not being reinstalled or provide detailed explanation as to how panels will be supported by the wood stringers, why such a change is being proposed, and how it would meet the like replacement requirements of the Stipulation.

4. In 4th and 5th paragraphs of Scope of Work, indicate which stringer or other part that the existing and replacement section rests attach to and provide nail description.

5. In Title Block, correct the number of faces.

Sheet 3 of 3
1. In Light Arm Mounting Detail, correct the size of the stringers that the light arms and conduit straps attach to and indicate that straps are to be replaced with like straps.

2. In elevations, include depiction of section rests.

3. In Title Block, correct the number of faces.

FIN.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/16/2016 AHINES2 OUT TO CUSTOMER Completed