02/17/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/24/2016 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Reqs Change BRC Comments

Below are comments on the authorized repair submittal for COT ID# 534 at 1698 North Freeway (T16BU00241).


Sheet 1 of 3
No comments

Sheet 2 of 3
1. In boxed note above Scope of Work, add ā€œUā€ to cover stringer fasteners being replaced.

2. Add note clarifying if light fixtures are to be removed and reinstalled or not.

3. Add standard note regarding removal of light fixtures from site, replicating Billboard Note #11 on Site Plan

4. In South Face Elevation, add vertical measurements from top of uprights to each stringer for each side.

Sheet 3 of 3
No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2016 KROBLES1 OUT TO CUSTOMER Completed