Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD - BLDG30days
Permit Number - T16BU00166
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/03/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/01/2016 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Reqs Change | BRC Comments Below are comments on the authorized repair submittal for COT ID# 334 at 730 East Broadway Boulevard (T16BU00166). Sheet 1 of 3 No comments Sheet 2 of 3 1. Add note clarifying whether or not light fixtures are to be removed and reinstalled, rotated, or otherwise moved from current fixed locations in course of work. 2. Add standard note regarding removal of light fixtures from site, replicating Billboard Note #11 on Site Plan 3. In East Elevation, add to panel designation that single two-foot wide sections are on the south ends of each face (per New Face Panel Section Detail on Sheet 3 of 3). Sheet 3 of 3 No comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/14/2016 | EGALLET1 | OUT TO CUSTOMER | Completed |