Plan Number: T15PI00023
Parcel: Unknown

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T15PI00023
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2016 CSALTZM1 DOT ENGINEERING REVIEW Approved Red Colt Ranch
T15PI00023

Reviewed by: E. Craig Saltzman 1/8/16

1. Sheet 2&3 of 3- Sidewalk
Change sidewalk width from 5’ to 6’ adjacent to Bonanza Ave. (collector) and 22nd St. (arterial) per Development Standards Section 10-01.4A1a
2) Sheet 2 of 3 - Need a detail for Curb Access Ramps at stations 16+69 Lt. & Rt. C.O.T. Detail 207 is for use with curb not header.
3) Sheet 2 of 3 - Note: "112 LF line of Sawcut, Trim Tack & Join, Match Existing Pavement". Need dimension or station to locate sawcut.
4) Sheet 3 of 3 - Cross Section "C"
Note reads: Proposed Pavement 2 ½” A.C. on 4” A.B.C.
Change to read: Proposed Pavement 2 ½" A.C. (C.O.T. Mix No. 2) on 4" A.B.C. and match existing pavement structural section
5) Sheet 3 of 3 - South East corner of Bonanza Ave. and Red Colt Rd. remove drainage swale from public R/W.
01/11/2016 JIM FEMLING DOT STREET MAINTENANCE REVIEW Denied Date: January 11, 2016
PROJECT NAME: Red Colt Ranch
PLAN #: I-2015-020
ACTIVITY NUMBER: T15PI00023
PROJECT REVIEWER: James Femling, Tucson DOT Streets & Traffic Maint.

Comments:

The TDOT Streets & Traffic Maintenance Division has reviewed the PIA plan and recommends denial/resubmittal. The following comment needs to be addressed in the subsequent plan submittal.

1. For maintenance purposes, use Type 3 scuppers instead of the Type 2.

If you have any questions, I can be reached at 791-3154 or James.Femling@tucsonaz.gov
01/15/2016 ERNIE ENCINAS DOT_ELEC REVIEW Passed PER SIGNED UTILITY PLAN RECEIPT, NO EXISTING UTILITIES THAT COULD CONFLICT WITH THE CONSTRUCTION OF THIS PROJECT, SIGNED BY ERNIE ENCINAS ON 12/09/15.
01/15/2016 LINZUNZA PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
01/15/2016 LINZUNZA PIA COORDINATOR OUT TO CUSTOMER Completed
12/11/2015 LINZUNZA UTILITY CLEARANCES COT STREETS DIVISION Denied
12/11/2015 LINZUNZA UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied
12/11/2015 LINZUNZA UTILITY CLEARANCES PC WASTEWATER MGMT Denied
12/11/2015 LINZUNZA UTILITY CLEARANCES QUEST COMMUNICATION Denied
12/11/2015 LINZUNZA UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied
12/11/2015 LINZUNZA UTILITY CLEARANCES COX COMMUNICATION Denied
12/11/2015 LINZUNZA UTILITY CLEARANCES SOUTHWEST GAS CORP Denied
12/11/2015 LINZUNZA UTILITY CLEARANCES EL PASO NATURAL GAS Denied
12/11/2015 LINZUNZA UTILITY CLEARANCES KINDER MORGAN ENERGY Denied
12/16/2015 GARY WITTWER DOT LANDSCAPE REVIEW Approved
12/21/2015 ZELIN CANCHOLA DOT TRAFFIC REVIEW Approved