Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: T15PI00017
Parcel: Unknown

Address:
5418 S PARK AV

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T15PI00017
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2015 LINZUNZA UTILITY CLEARANCES COT STREETS DIVISION Completed
07/20/2015 LINZUNZA UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
07/20/2015 LINZUNZA UTILITY CLEARANCES PC WASTEWATER MGMT Completed
07/20/2015 LINZUNZA UTILITY CLEARANCES QUEST COMMUNICATION Completed
07/20/2015 LINZUNZA UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
07/20/2015 LINZUNZA UTILITY CLEARANCES COX COMMUNICATION Completed
07/20/2015 LINZUNZA UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
07/20/2015 LINZUNZA UTILITY CLEARANCES EL PASO NATURAL GAS Completed
07/20/2015 LINZUNZA UTILITY CLEARANCES KINDER MORGAN ENERGY Completed
07/28/2015 JOSE ORTIZ DOT TRAFFIC REVIEW Approved
07/29/2015 GARY WITTWER DOT LANDSCAPE REVIEW Approved
07/29/2015 RICHARD LEIGH DOT ENGINEERING REVIEW Approv-Cond July 28, 2015


SUBJECT: Public Roadway Improvement Plans for Minorka Road at Rio Viejo U-2015-013 T15PI00017

PROJECT REVIEWER: Richard Leigh, TDOT, TDOT Eng. Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and recommends a conditional approval. The following comments need to be addressed and plans revised prior to submittal of the mylar plan set for signatures. Please include a response letter addressing the following comments and return redlined drawings with subsequent submittal.

1. Include the plan number "U-2015-013" in the title block of each sheet.

2. Include the PIA activity number "T15PI00017 on cover sheet.

3. Sheet 1: Revise Arizona Blue Stake label with latest version. Arizona 811 has a new, updated label for engineering prints and plans and it is now available in JPG, PDF and DXF formats on their website under "Resources" - http://www.arizona811.com/resources.

Please Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsonaz.gov
08/06/2015 LINZUNZA PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
08/06/2015 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved
08/06/2015 LINZUNZA PIA COORDINATOR OUT TO CUSTOMER Completed