Plan Number: T15PI00004
Parcel: Unknown

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T15PI00004
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2015 LINZUNZA UTILITY CLEARANCES COT STREETS DIVISION Denied
03/03/2015 LINZUNZA UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied
03/03/2015 LINZUNZA UTILITY CLEARANCES PC WASTEWATER MGMT Denied
03/03/2015 LINZUNZA UTILITY CLEARANCES QUEST COMMUNICATION Denied
03/03/2015 LINZUNZA UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied
03/03/2015 LINZUNZA UTILITY CLEARANCES COX COMMUNICATION Denied
03/03/2015 LINZUNZA UTILITY CLEARANCES SOUTHWEST GAS CORP Denied
03/03/2015 LINZUNZA UTILITY CLEARANCES EL PASO NATURAL GAS Denied
03/03/2015 LINZUNZA UTILITY CLEARANCES KINDER MORGAN ENERGY Denied
03/04/2015 GARY WITTWER DOT LANDSCAPE REVIEW Approved
03/24/2015 ZCANCHO1 DOT TRAFFIC REVIEW Reqs Change March 24, 2015


SUBJECT: Walmart Neighborhood Market at Tucson Blvd and Drexel Rd
PIA Plan I-2015-002, DSD Activity #T15PI00004

PROJECT REVIEWER: Zelin Canchola,
TDOT Review Section

RESUBMITTAL REQUIRED: DOT Review Section has reviewed the PIA Plan for Traffic Engineering. Resubmit with the following redlines on sheets 10 and 11 of 13

1. Add general notes from PCDOT/TDOT Pavement Marking Design Manual Sheet 2-1

2. Each plan sheet is to list quantities and descriptions for striping materials including number and type of RPMs, lineal footage quantities of longitudinal and traverse striping, arrows, words and symbols (i.e., turn arrows, only, stop ahead etc.) - From Pavement Marking Design manual, Pima County/City of Tucson pavement marking Plan Review Checklist. Page 1-5

3. Show opening width of left turn bay on Drexel

4. Show sign and size of speed limit and stop signs

5. Bike lanes on Tucson Blvd. shall be 5 feet minimum.



If you have any questions I can be reached at 837-6659 or zelin.canchola@tucsonaz.gov
04/17/2015 LINZUNZA PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
04/17/2015 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied Resubmittal required by Streets & Traffic Maintenance. Jim Femling - Reviewer
04/17/2015 LINZUNZA PIA COORDINATOR OUT TO CUSTOMER Completed
04/17/2015 LINZUNZA DOT ENGINEERING REVIEW Denied Date: April 17, 2015
PROJECT NAME: Offsite Improvements plans for Walmart Neighborhood Market @ Tucson Blvd and Drexel Rd.
PLAN #: I-2015-002 ACTIVITY NUMBER: T15PI00004
PROJECT REVIEWER: E. Craig Saltzman, P.E., Engineering Review, City of Tucson DOT

Comments:

The TDOT Engineering Review Section has reviewed the PIA Plan and recommends resubmittal. The following comments need to be addressed in the subsequent plan submittal.

1) Use City of Tucson P.I.A. Guidelines & Check list - the guidelines can be found at http://www.tucsonaz.gov/files/transportation/PIA_guidelines&checklist.pdf

2) See Pima County City of Tucson Joint Standard Details for drafting symbols & line weights.

3) Sht. 1 of 13 - First blocked note which reads "All Roadway, Parking lot,…standards will be used." Remove and substitute with the following - All work within the public Right-of-way shall conform to Pima County -City of Tucson Standard Specifications and Details 2003.

4) Sht. 2 of 13 - City of Tucson Paving Notes:

6. Add "a minimum of "prior to the wording "60 MIL"
7. Add "a minimum of "prior to the wording "90 MIL"
13. Remove 701 and replace with 701-3.08 & 701-3.09
"Note: Asphalt scarring…stripe." After the word stripe ADD a iminium of 1 Ft. past the edge of stripe (1Ft. + 1Ft. + stripe width = minimum coverage width).
5) Sht. 2 of 13 - Abbreviations and Legend See Pima County /City of Tucson Standard Specification and Details.

6) Sht. 2 of 13 - ENGINGEERING NOTES - Add the following note. Prior to starting any work the contractor shall have an approved Storm Water Prevention Plan - SWPP.

7) Sht. 1, 3, &10 "BASIS of Bearing "- ADD of Maps & Plats following "as shown in Book 51 Page 25"

8) Sht. 4 PAVING SECTION - Match existing pavement structural section or better. See plans I-98-51 and I-81-59B. Show percent compaction of subbase.

1 ½" Mix #3
3 ½' Mix #1
6' AB
9) Sht. 5 Paving Section - see comments for Sht.4

10) Sht. 5 - Include Detail for City of Tucson Thickened Edge Detail along edge of strip paving (2 Ft. wide and 1 Ft. thick tapering back to pavement section).

11) Sht. 6 Remove 8' X 22' bus Pad from roadway and locate from back of curb toward sidewalk ( Bus Pads are used for the bench and shelter) Locate sidewalk to accommodate Bus Pad.

12) Sht. 6 Use City of Tucson Plan and Profile layout.

13) Sht. 6 Need Curve Data tables for horizontal curves

14) Sht. 6 & 7 Maintain gutter slope across driveways

15) Sht. 6 Use City of Tucson Station and Out format.

16) Sht. 7 Handrail - call out Beginning and End stations & outs

17) Sht. 7 RCP culvert call out Station ,Out And Skew angle from Tucson Blvd. construction stationing

18) Sht. 7 Avenida Malcote - saw cut limits past manhole - same distance as used on sides.

19) Sht. 7 Island Transition to Turn Bay remove angle points and replace with horizontal curves - Sta. 18+97.67 and Sta. 20+03.73 (see plan I-81-59B for reference).

20) Sht. 7 Stationing - See P.I.A. Guidelines Office Procedure No. 8-1552-002 Sht. 4

21) Sht. 7 Need Curve Data tables for horizontal curves

22) Sht. 8 Need Bearing and Stations for Construction center line along Tucson Blvd. and Drexel Rd.

23) Sht. 9 Plan View - Call out 48" RCP Culvert and Station and out.

24) Sht. 9 48" Pipe culvert grade to drain from outlet.

25) Sht. 10 Left Turn Bay Remove- Arrow legend at sta. 10+65, Only legend at sta. 11+15, and Arrow legend at sta. 11+75

26) Sht. 10 Call out - Refresh stop bar and cross walk striping at eastside of intersect Tucson Blvd. and Drexel Rd.

27) Sht. 10 Add City of Tucson general Notes for Pavement Marking and Signing. Contact Diahn Swartz at Diahn.swartz@tucsonaz.gov for copy of nites.

28) Sht. 13 Head Wall Detail - Remove CMP Bevel Detail. Remove all diameters of pipe not being used on this job.

29) Wy the 50' radius?

If you have any questions, I can be reached at 791-4259 or Craig.Saltzman@tucsonaz.gov