Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T15OT01258
Parcel: 11007341A

Address:
4245 E GRANT RD

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T15OT01258
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2015 JASON GREEN ENGINEERING REVIEW Reqs Change DATE: September 29, 2015
SUBJECT: 4245 E Grant Road- Cell Tower & CMU Wall Installation
TO: Maxwell Winn
LOCATION: T13S R14E Sec34, Ward 6
REVIEWERS: Jason Green, CFM
ACTIVITY: T15CM06498 (Building Plan) and T15OT01258 (Floodplain Use Permit)

SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the Building Plan (T15CM06498) and Floodplain Use Permit (T15OT01258) for the above referenced property and does not recommend approval of the at this time.

The subject property is located within a Shaded Zone X 100-year floodplain as shown on the Flood Insurance Rate Map (FIRM), Community- Panel No. 040073-04019C-1694L, effective date June 16, 2011.

Per Section 26-5.2 of the Tucson Code no development, storage of materials or equipment or other uses shall be permitted which acting alone or in combination with existing uses, create a danger or hazard to life or property. In order to process your application for development within the floodway fringe of the Columbus Wash the following information is required:

BUILDING PLAN:

1) TC Sec.26-11.2.e: Provide an engineering study prepared by a state-registered engineer outlining the effects the development will have on the flow of water through the area being developed and the surrounding areas. Per the rezoning conditions a drainage statement is required for development of the site to calculate the water surface elevation, elevation of the equipment, encroachment, wall openings, etc.

2) TC Sec.26-5.2.5: Revise the building plan and CMU wall detail to label and dimension the required wall openings to prevent encroachment within the floodplain per the required drainage statement that shows the enclosure will not increase the base flood elevation more than one-tenth of a foot. The openings shall provide a total net area of not less than one square inch for every square foot of area enclosed, excluding any bars, louvers, or other covers of the opening. The bottom of the openings must be no higher than one foot above the higher of the exterior or interior grade or floor immediately below the opening and must be located with a minimum of 1 opening on each wall, but preferably with 2 opening on each wall.

3) TC Sec.26-5.2.10: Provide a note on the Building Plan to clearly state that all structures, material or equipment will be anchored to prevent flotation. Specifically for equipment such as generators that utilize gas or oil components.

4) TC Sec.26-11.2.h: An Elevation Certificate (FEMA Form 086-0-33) must be prepared by a state registered land surveyor and submitted to our office prior to Final Electrical and Building Final inspections. The ELCERT will be issued with the Building Permit with all applicable Community Information filled out.

GENERAL COMMENTS:

Please provide a revised Building Plan and drainage statement with revised details that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

For any questions or to schedule meetings call me at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
11/03/2015 KROBLES1 OUT TO CUSTOMER Completed