Permit Number: T15OT00030
Parcel: 116161870

Address:
925 N CONTZEN AV

Review Status: Active

Review Details: FLOODPLAIN

Permit Number - T15OT00030
Review Name: FLOODPLAIN
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2015 JASON GREEN ENGINEERING REVIEW Approved January 12, 2015
FLOODPLAIN USE PERMIT NO.: T15OT00030
ADDRESS: 925 N Contzen Ave Tucson, Arizona 85705
PROPERTY OWNER: Irene Molina
450 N Avenida Carina Tucson, AZ 85745

The applicant is authorized to use a portion of the FEMA Special Flood Hazard Area Zone AO1 floodplain per the Flood Insurance Rate Maps 04019C2276L, specifically described as:

A portion of Parcel 116-16-1870

For the purpose of constructing a new single family residence.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and is particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Unified Development Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

This floodplain use permit is issued with the following 8 conditions:

1) This project is located in a mapped regulatory FEMA Special Flood Hazard Area Zone AO1 floodplain per the Flood Insurance Rate Maps 04019C2276L.

2) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.

3) For purposes of this permit the following flood elevations shall be used for the building:
Base Flood Elevation (BFE) = 1.0 feet Highest Adjacent Grade
Regulatory Flood Elevation (RFE) = 2.0 feet Highest Adjacent Grade
Building is to have lowest finished floor elevated at or above the Regulatory Flood Elevation (RFE) and lowest point of any attached appliances is to be at or above the Regulatory Flood Elevation (RFE).

4) Floodplain Approval of elevation certificate, prepared by an Arizona State Registered Land Surveyor, is required prior to the 1010/1015 inspection (P2S) and prior to finished construction or Final Inspection (P2F). The Elevation Certificate must include the identity and elevation of the lowest service equipment/machinery servicing the building as well as the identity and location of all other equipment/machinery servicing the building.

5) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T15OT00030 FOR INFORMATION PLEASE CALL 791-5550."

6) Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval.

7) All work shall conform to the approved building plan, T15CM00127, which is made part of this permit.

8) This permit is specific to the improvements for 925 N Contzen Ave as indicated on the approved plans. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit.

Renewal of this permit will require a new application, review and approval of that application by the City of Tucson Planning & Development Services Department, Engineering Division. This permit may be renewed for up to one year at the sole discretion of the City Engineer or designated representatives.

This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit.

APPLICANT NAME: Troy Williams
ADDRESS: 4561 W Annabelle St Tucson, Arizona 85741
PHONE: 520-248-0312

(EXPIRATION DATE) Month: 01 Day: 09 Year: 2016

SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/19/2015 CPIERCE1 APPROVAL SHELF RECEIVED