Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T15CM08972
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/09/2016 | KROBLES1 | ENGINEERING | REVIEW | Needs Review | |
| 03/09/2016 | KROBLES1 | BUILDING-RESIDENTIAL | REVIEW | Needs Review | |
| 12/29/2015 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | P&DS TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: T15CM08972 517 S. Star Avenue Permit existing Master bed & bath addition and detached ramada TRANSMITTAL: December 29, 2015 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-3 zone (UDC 4.7.12). A single-family residence is a permitted use in this zone (Table 4.8-2). See Use Specific Standards 4.9.7.B.6. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Based on a wall height 10'-10" the require perimeter yard setback to the north property line is 7'-3", proposed perimeter yard setback is 6'-0". |
| 12/29/2015 | SSHIELD1 | NPPO | REVIEW | Passed |