Permit Number: T15CM08965
Parcel: 106020650

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM08965
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2016 KEN BROUILLETTE FIRE REVIEW Passed THESE DRAWINGS NEED THE STATE OF ARIZONA FIRE MARSHAL APPROVAL
01/19/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S1 (GENERAL STRUCTURAL NOTES-FOUNDATIONS); GEOTECHNICAL REPORT (SHEET 5): THE NOTES INDICATE AN ALLOWABLE SOIL BEARING VALUE OF 3000 PSF AT 2'-0" BELOW FINISH GRADE, WHILE THE GEOTECHNICAL REPORT TABLE INDICATES 2500 PSF AT THAT DEPTH. PLEASE CLARIFY.
2. SHEET S2; DETAIL 09: NOTES 10 AND 11 HAVE THE FOOTING THICKNESS AND COLUMN EMBEDMENT REVERSED FOR F1 AND F2. PLEASE REVISE.
3. SHEETS S3 AND S4 (DRILLED PIER SCHEDULE); STRUCTURAL CALCULATIONS (SHEET 38): THE CALCULATIONS INDICATING THE REQUIRED DRILLED PIER DEPTHS DO NOT MATCH THE DEPTHS SHOWN ON SHEETS S3 AND S4. PLEASE CLARIFY.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/21/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/26/2016 KROBLES1 OUT TO CUSTOMER Completed