Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM08961
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/08/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A-1; LIFE SAFETY DATA: THE 'COMMON PATH OF TRAVEL' INDICATES 75' IS ALLOWED, AND THE PROPOSED DISTANCE IS 100' OR LESS. THE PROPOSED EXCEEDS THE ALLOWABLE. PLEASE CLARIFY. 2. SHEET A-1; LIFE SAFETY DATA: TABLE 1016.1 IS REFERENCED FOR THE TRAVEL DISTANCE LIMIT. PLEASE REVISE THE REFERENCE TO TABLE 1016.2. 3. SHEET A-1; LIFE SAFETY DATA: TABLE 1021.1 IS REFERENCED FOR THE NUMBER OF EXITS. PLEASE REVISE THAT REFERENCE (NO TABLE 1021.1 IN THE 2012 IBC). 4. SHEET A-1; PLUMBING FIXTURE DATA: THE REQUIRED WATER CLOSETS IS INDICATED AS TWO EACH. ONLY ONE EACH (MALE AND FEMALE) IS REQUIRED PER TABLE 2902.1. PLEASE REVISE. 5. SHEET A-1; CODE DATA: A NOTE FOR THE ACCESSIBILITY CODES INDICATES TO USE THE MOST RESTRICTIVE OF THE 2009 ICC/ANSI AND THE 2010 ADA. WE WILL ONLY CONSIDER THE ICC/ANSI FOR THIS PROJECT. PLEASE REVISE THE NOTE. 6. SHEET A-4; FLOOR PLAN: THE WALL BETWEEN TENANT SPACES MUST MEET THE FIRE RESISTANCE RATING PER THE IBC SECTION 708. PLEASE INDICATE ON THE PLAN THE SPECIFIC DETAIL ON SHEET A-6 FOR THE CONSTRUCTION OF THIS WALL. IN ADDITION, INDICATE THE WALL HAS BEEN CONSTRUCTED PER THE REQUIREMENTS OF U.L DESIGN NUMBER U419 (SHEET A-15), AND INCLUDE A REFERENCE TO THE PERMIT ACTIVITY NUMBER THAT THIS WALL WAS CONSTRUCTED UNDER. 7. SHEET A-6.1; SECTION 4: PLEASE INDICATE THE CONNECTION OF THE DIAGONAL BRACE TO THE EXISTING WALL, AND PROVIDE A DETAIL FOR THE CONNECTION OF THE DIAGONAL BRACE TO THE STUD WALL. 8. SHEET P-1; WATER HEATER DETAIL: PLEASE INDICATE ON THE DETAIL THE PLATFORM ANGLE SIZES AND ANCHOR SIZE, QUANTITY, AND LENGTH INTO THE SUPPORTING STUD WALL. INDICATE ANY WALL BRACING/STIFFENERS AS REQUIRED. 9. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
01/08/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/08/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Termination of the excess pressure relief from the water heater over an elevated service sink is not approved location. Reference: Section 504.6 (6), IPC 2012. |
01/08/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012. 2. Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012. 3. Alterations of an existing building in which the existing ceiling or wall cavities are exposed, shall have the exposed cavities filled with insulation. Reference: Section 101.4.3, IECC 2012. 4. Demonstrate energy code compliance for the alterations to the building envelope based on the current code. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012. 5. Specify the required U-factors and Solar Heat Gain Coefficients (SHGC) for the fenestration products on the architectural drawings. The U-factors and Solar Heat Gain Coefficients (SHGC) for the fenestration products shall be NFRC-certified. Reference: Sections C103.2 and C303.1.3, IECC 2012. 6. Verify that the specified programmable thermostats are capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy. Reference: Section C403.2.4.3.3, IECC 2012. |
01/11/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide full compliance with the IECC for interior lighting. |
12/29/2015 | CARL SCHULTZ | FIRE | REVIEW | Approved |