Permit Number: T15CM08926
Parcel: 11204012B

Address:
2533 E GLENN ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T15CM08926
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2016 EGALLET1 ENGINEERING REVIEW Needs Review
03/11/2016 EGALLET1 BUILDING-RESIDENTIAL REVIEW Needs Review
12/23/2015 STEVE SHIELDS ZONING REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Steve Shields
Lead Planner

PROJECT:
T15CM08926
2533 E. Glenn Street
Enclose Porch

TRANSMITTAL: December 23, 2015

COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

Based on a wall height of 7'-11" the required perimeter yard setback to the north property line is 6'-0", proposed 1'-0".
12/23/2015 SSHIELD1 NPPO REVIEW Passed