Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T15CM08921
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/07/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/08/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/08/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 07/20/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Outdoor lighting code compliance as discussed with Polo Padilla. #2. Flag pole lighting to be included in Outdoor lighting calc's. |
| 07/21/2016 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | Approval of development package DP15-0194 is required prior to approval of the building plan. The building plans must conform to the approved development package plans. Once the development package has been approved Zoning is willing to provide and over the counter review. |