Permit Number: T15CM08900
Parcel: 134031450

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM08900
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET 6; SITE PLAN: DOES THE ACCESSIBLE ROUTE TO THIS CANOPY MEET THE REQUIREMENTS OF THE ICC/ANSI SECTIONS 402 AND 403? PLEASE VERIFY ON THE PLANS WITH A NOTE.
2. SHEET 6; SITE PLAN: PER THE IBC SECTION 2902.3, PUBLIC TOILET FACILITIES ARE REQUIRED IN STRUCTURES AND TENANT SPACES INTENDED FOR PUBLIC UTILIZATION. PLEASE VERIFY ON THE DRAWINGS WITH A NOTE INDICATING THE REQUIREMENTS OF THE IBC SECTION 2902.3.2 ARE MET.
3. SHEET A4.1; ELEVATIONS D AND E: THE IBC SECTION 1109.11 REQUIRES THE TABLE AND WORK SURFACE AREAS TO BE ACCESSIBLE. THE ICC/ANSI SECTION 902.4 INDICATES A MAXIMUM 34" HEIGHT ABOVE THE FLOOR OF THESE AREAS. PLEASE REVISE.
4. SHEET S1.0; GENERAL STRUCTURAL NOTES (FOUNDATIONS): NOTE 1 INDICATES A SOIL REPORT WAS USED FOR THIS PROJECT. PLEASE PROVIDE A COPY OF THAT REPORT FOR REVIEW.
5. SHEET S1.3 (BEAM SCHEDULE); STRUCTURAL CALCULATIONS: WHERE IS THE B1/B2 DESIGN INDICATED IN THE CALCULATIONS? SHEET 2 INDICATES AN 8" X 8" DF-L NO. 2 BEAM, BUT THE BEAM SCHEDULE INDICATES A 4X10. PLEASE CLARIFY.
6. SHEET S1.3 (SHEAR WALL SCHEDULE); STRUCTURAL CALCULATIONS: WHERE IS THE SHEAR WALL REQUIRED NAILING, HOLDOWNS, AND FOUNDATION DESIGNS INDICATED IN THE CALCULATIONS? PLEASE PROVIDE.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/24/2015 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/28/2016 EGALLET1 OUT TO CUSTOMER Completed