Review Details: REVISION - - 1ST

Permit Number - T15CM08899
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. THE LOBBY AREA WITH THE DELTA 4 CHANGE INDICATES STEEL COLUMNS (4) ADDED TO SUPPORT AN EXISTING STEEL LINTEL. THE NOTE INDICATES TO SEE STRUCTURAL. WHERE IS THIS STRUCTURAL INFORMATION LOCATED? PLEASE VERIFY.
2. IN THE LOBBY AREA, PLEASE INDICATE THE SIZE OF THE NEW STEEL COLUMNS. CURRENTLY HAVE INDICATED A 6 X 4 STEEL COLUMN.
3. IN THE LOBBY AREA AT THE NEW TUBE COLUMN LOCATIONS, PLEASE INDICATE WITH A DETAIL HOW THE EXISTING LINTEL WILL ATTACH TO THE NEW COLUMN, AND A DETAIL INDICATING HOW THE NEW STEEL COLUMNS WILL ATTACH TO THE EXISTING SLAB.
04/11/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the changes to M1.1; the revision block shows a delta 4 dated 4/8/16 but the newest change on the drawing is labeled as a delta 2. The approved drawings have a delta 1 only.
2. Explain the clouded revisions (delta 4) to the outdoor air calculations. The calculations show zone supply air flows that have not changed from the approved drawings.
04/12/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2016 AHINES2 OUT TO CUSTOMER Completed