Permit Number: T15CM08899
Parcel: 116154960

Address:
1714 W ANKLAM RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM08899
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2016 KEN BROUILLETTE FIRE REVIEW Reqs Change 1. The second exit goes through a breakroom. This is similiar to a kitchen per Section 1014.2 (4). Please clarify how this room acceptable to be used as an exit path.
01/22/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/22/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the mechanical design as required to avoid using the corridor as a return air duct (see room 116). Reference: Section 601.2, IMC 2012.
2. Review the description of the treadmill room used for the ventilation calculations; would an aerobics room be a better description than a patient room? Reference: Section 403.3, IMC 2012.
01/22/2016 ROBERT SHERRY WATER REVIEW Completed
02/01/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET TS1.0; PLUMBING FIXTURE CALCULATIONS; CODE STUDY (OCCUPANT LOADS): IN THE PLUMBING FIXTURE CALCULATIONS, A USABLE AREA OF 4999 SF IS INDICATED, AND AN OCCUPANT LOAD OF 50 IS CALCULATED. IN THE CODE STUDY, THE ACTUAL GROSS AREA OF 5680 SF IS INDICATED AND AN OCCUPANT LOAD OF 57 IS CALCULATED. THE IBC TABLE 1004.1.2 INDICATES FOR BUSINESS AREAS, THE OCCUPANT LOAD FACTOR IS 100 GROSS SF/OCCUPANT. THE PLUMBING REQUIREMENTS MUST BE BASED ON THE OCCUPANCY CALCULATION. PLEASE REVISE FOR 57 OCCUPANTS.
2. SHEET TS1.0; CODE ANALYSIS DATA: THE ICC/ANSI INDICATES THE 2011 EDITION. PLEASE REVISE TO THE 2009 EDITION.
3. SHEET TS1.0; GENERAL BUILDING SUMMARY: THE ALLOWABLE BUILDING AREA MAY BE INCREASED BY 300% PER THE IBC SECTION 506.3. PLEASE REVISE.
4. SHEET TS1.0; ALLOWABLE AREA CALCULATION: THE TABLE INDICATES N/A FOR AREA INCREASE FOR SPRINKLERS. PLEASE REVISE PER THE IBC SECTION 506.3.
5. SHEET A1.0; FIRST FLOOR PLAN: THE SECOND EXIT FOR THIS SPACE IS THROUGH THE BREAK ROOM. PER THE IBC SECTION 1014.2(2), AN EXIT ACCESS SHALL NOT PASS THROUGH A ROOM THAT CAN BE LOCKED. THE HARDWARE ON DOOR 112 (SET 4 ON SCHEDULE SHEET A4.0) INDICATES A PASSAGE LOCKSET. PLEASE VERIFY.
6. SHEET A1.0; FIRST FLOOR PLAN: PER THE IBC SECTION 1005.7.1, DOORS IN ANY POSITION SHALL NOT REDUCE THE REQUIRED MEANS OF EGRESS WIDTH BY MORE THAN ONE HALF. DOORS 111 IN THE STORAGE ROOM, 133 IN THE DRUG CLOSET, AND 137 IN THE SERVER ROOM DO NOT MEET THAT REQUIREMENT. PLEASE REVISE.
7. SHEET A3.0; EXTERIOR ELEVATIONS: IS THERE A NORTH ELEVATION TO BE INCLUDED IN THE DRAWINGS? PLEASE VERIFY.
8. SHEET A5.0; ELEVATION 6: THE HEIGHT OF THE COFFEE COUNTER SHOULD BE 34" MAXIMUM ABOVE THE FINISH FLOOR. PLEASE VERIFY.
9. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/03/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/08/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/09/2016 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change DATE: February 10, 2016
DUE DATE: February 16, 2016
SUBJECT: TI, Medical Office
TO: Evan Sar Eglin
LOCATION: 1714 W. Anklam Road
REVIEWERS: Paul Baughman, PE, CFM
ACTIVITY: T15CM08899
SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the proposed Development Plan Package. The main issue that needs to be addressed is the conveyance of roof drainage under the new adjacent pedestrian way. This requirement is being in only the proposed expansion area.
The following items need to be addressed:
1) Approval of the floodplain use permit is required prior to approval of this plans set.
2) Per January 20, 2016 TIF image on Pima County Assessor's office for this parcel, there is existing roof drainage being conveyed beneath the pedestrian way by the front door and to the pavement surface. The pedestrian area where this roof drainage is being conveyed is being replaced as part of this plan per details 1 and 5 on sheet A3.1. Per TSM 7-01.4.3E please update details 1 and 5 on sheet A3.1 to show how this roof drainage will continue to be routed under the pedestrian way. Please also add dimensions to these details to show any impact to existing parking conditions. Further review comments may be forthcoming based on any proposed layouts.
3) The valuation for the improvements ($250,000) exceeds 50% of the existing value of the property as shown on the Pima County Assessors office for parcels 116-15-4970 ($168, 525) and parcel 116-15-4960 ($250,950). Per Chapter 26-4 (3) of the Tucson Code if the value of the building improvements exceeds 50% of the value of the existing structure the building must be shown to comply with existing floodplain code. Please either show that the improvements are do not exceed 50% of the existing value by providing a current appraisal or show the existing structure is compliant with the existing floodplain code. This means providing an elevation certificate from a land surveyor and a base flood elevation from a Civil Engineer.
If you have any comments questions or wish to discuss new information, please call or email me at 520-837-5007 or paul.baughman@tucsonaz.gov.