Permit Number: T15CM08845
Parcel: 14029023B

Address:
3430 E GLOBAL LP

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T15CM08845
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2016 KEN BROUILLETTE FIRE REVIEW Reqs Change Electrical plan only indicates one exit to south of bulding, exiting plan appears to indicate two exits towards south. Additionally, the room to the south is annotated as existing inventory, which to me means storage. That would mean we are exiting from a lower hazard area through a higher hazard. Please indicate how compliance with section 1014.2 (4) is being obtained.
Also, please provide a Hazardous Material Inventory
Statement indicating what chemicals/materials are being used in the new cleanrooms.
01/21/2016 ROBERT SHERRY WATER REVIEW Completed
01/21/2016 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/22/2016 FERNE RODRIGUEZ OUT TO CUSTOMER Completed