Permit Number: T15CM08820
Parcel: 12308082A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM08820
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/17/2015 STEVE SHIELDS ZONING REVIEW Approved
12/17/2015 LOREN MAKUS ENGINEERING REVIEW Approved
12/21/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Appliances (e.g. espresso machines, coffee makers, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
2. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
12/21/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/21/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/21/2015 KEN BROUILLETTE FIRE REVIEW Approved
12/21/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/21/2015 ROBERT SHERRY WATER REVIEW Completed
12/22/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved