Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM08779
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/06/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 2: WE WILL INCLUDE THE RACKING SUBMITTAL AS PART OF THE ORIGINAL PROJECT. HOWEVER, FOR THE 10 FOOT HIGH RACKS, PLEASE PROVIDE A DETAIL OF HOW THESE ARE CONNECTED TO THE BUILDING. THE PHOTO WILL NOT SUFFICE FOR THAT CONNECTION. |
01/06/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
01/07/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved |