Permit Number: T15CM08779
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM08779
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2016 EGALLET1 FIRE REVIEW Needs Review
12/16/2015 STEVE SHIELDS ZONING REVIEW Approved
12/16/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
12/16/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/16/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEETS A-1.0, A-2.0, A-3.1, A-4.0, A-5.1, AND A-5.2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) SHALL BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE DIMENSIONS AND VERBIAGE ON THESE SHEETS TO MEET THAT REQUIREMENT.
2. SHEET A-1.0; FLOOR PLAN: THE RACKS/SHELVES REQUIRE A SEPARATE PERMIT. THE FIXTURES SHOWN ON SHEET A-1.0 CAN BE USED FOR THIS PERMIT. FOR SHELVING OVER 6' TALL UP TO 12' TALL, PROVIDE A DETAIL ON THE PLAN THAT SHOWS THE CONNECTION OF THE SHELF TO THE FLOOR. IF SHELFS EXCEED 12' IN HEIGHT, A STRUCTURAL ANALYSIS MUST ALSO BE SUBMITTED ALONG WITH THE CONNECTION DETAIL.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/16/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/17/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Condensate drains shall be terminated at an approved disposal location. Termination over a splash block on the roof (see detail 3/M1) is not an approved disposal location. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
12/17/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/17/2015 ROBERT SHERRY WATER REVIEW Completed