Permit Number: T15CM08773
Parcel: 14043011A

Address:
7211 S PARK AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T15CM08773
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/19/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the component descriptions in the envelope compliance certificate of COMcheck to match the actual construction shown on the architectural drawing (e.g. the roof has R-30 cavity insulation and no continuous insulation; the exterior walls are shown with unspecified cavity insulation but no continuous insulation - see A-301). Provide either the NFRC documentation for the fenestration or state the required maximum NFRC-certified U-factor and SHGC values for the fenestration components on the drawings. [Initial comment: Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code (e.g. COMcheck envelope compliance). Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.]
04/19/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed