Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T15CM08773
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/15/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/19/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the component descriptions in the envelope compliance certificate of COMcheck to match the actual construction shown on the architectural drawing (e.g. the roof has R-30 cavity insulation and no continuous insulation; the exterior walls are shown with unspecified cavity insulation but no continuous insulation - see A-301). Provide either the NFRC documentation for the fenestration or state the required maximum NFRC-certified U-factor and SHGC values for the fenestration components on the drawings. [Initial comment: Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code (e.g. COMcheck envelope compliance). Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.] |
| 04/19/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |