Permit Number: T15CM08746
Parcel: 14042002A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM08746
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify the route for the pan drain from the water heater. It is shown running approximately 12" below the suspended ceiling in the entry lobby. [Initial comment: Clarify the termination point for the water heater T&P drain, and the water heater pan drain: there is no mop sink identified in the suite.]
12/18/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved