Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM08744
Parcel: 11005014C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM08744
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/17/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change The prior C of O in incorrect. The building does not have fire sprinklers. The increase of occupant load will require the building to be fire sprinklered. Ken B
12/23/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. A note requiring the addition of a flow control is shown for two hand sinks, a floor sink receiving the drainage from an ice maker, and a floor sink receiving the discharge from a prep sink. Provide a detail showing how these flow controls are to be installed and the flow rate each device is to allow. Reference: Section 303.2, IPC 2012.
2. Appliances (e.g. soda dispensers, beverage dispensers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.