Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM08744
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/17/2015 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | The prior C of O in incorrect. The building does not have fire sprinklers. The increase of occupant load will require the building to be fire sprinklered. Ken B |
12/23/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. A note requiring the addition of a flow control is shown for two hand sinks, a floor sink receiving the drainage from an ice maker, and a floor sink receiving the discharge from a prep sink. Provide a detail showing how these flow controls are to be installed and the flow rate each device is to allow. Reference: Section 303.2, IPC 2012. 2. Appliances (e.g. soda dispensers, beverage dispensers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012. |