Permit Number - T15CM08700
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/14/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 12/14/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Verify that the location of the exhaust outlet for EF-1 is greater than 3-feet from any building opening. Reference: Section 501.3.1 (3), IMC 2012. |
| 12/14/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/14/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 12/14/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Coordinate the waste and vent riser diagram with the plumbing plan. Clarify the location of the cleanout shown for the new water closet, P3. |
| 12/14/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/14/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 12/15/2015 | EGALLET1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/15/2015 | EGALLET1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |