Permit Number: T15CM08677
Parcel: 11105063J

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM08677
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Per keynotes 1 and 14 on sheet A5, the wall insulation is not continuous but is a cavity-type insulation and it has a U-value of 0.084 BTUH/SF/degree Fahrenheit, not 0.050 BTUH/SF/degree Fahrenheit. [Initial comment: Provide sufficient detail on the drawings to show that the submitted COMcheck analysis applies to the proposed addition to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.]
2. Provide plans sealed by an Arizona Registrant (sheets A1 through A5). Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
01/26/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/29/2016 KROBLES1 BUILDING-COMMERCIAL REVIEW Needs Review
01/29/2016 KROBLES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review