Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM08664
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/10/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 12/10/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 12/11/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the ventilation calculations. The corridor requires 0.6 CFM per square foot and the meeting room has a default population of 50 people per 1,000 Square feet. |
| 12/11/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/11/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/11/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/11/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 12/11/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/14/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |