Permit Number: T15CM08632
Parcel: 13321074A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM08632
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/01/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the two vents for the gravity grease interceptor so that they rise vertically to at least 6" above the flood rim of the grease interceptor before they connect. Reference: Section 905.5, IPC 2012. [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.]
02/16/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/19/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/22/2016 FRODRIG2 ZONING REVIEW Needs Review